Eaton Electrical Power Supply 3105 UPS User Manual

Powerware 3105 UPS  
UserÊs manual  
UserÊs Manual 350-700VA Rev B  
 
Powerware 3105 UPS  
UserÊs manual  
1023921 Revision B  
Contents  
Introduction .................................................................................................................. 4  
Features .................................................................................................................... 4  
Unit inspection .......................................................................................................... 4  
Safety Instructions ...................................................................................................... 5  
Battery connection required before use! .................................................................... 6  
Connecting the Battery: ............................................................................................ 6  
Installation and Operation: .......................................................................................... 6  
Typical applications .................................................................................................. 7  
Indicators ..................................................................................................................... 7  
Battery replacement procedure: ................................................................................. 8  
Status Indicators ...................................................................................................... 9  
LED and Alarm Status Table ................................................................................... 10  
Specification............................................................................................................ 10  
Troubleshooting ...................................................................................................... 11  
Service and Support .................................................................................................. 11  
3
UserÊs Manual 350-700VA Rev B  
 
Introduction  
The Powerware 3105 uninterruptible power system (UPS) filters the input line from  
line disturbances and protects your sensitive electronic equipment from three common  
power problems such as power failures, power sags and power surges.  
Features:  
Six outlets  
- Three with surge and battery backup protection  
- Three with surge protection only  
Data Line (Internet faxꢁmodemꢁDSL) or telephone line surge protection jacks  
Cold Start capability  
Proprietary LanSafe Power management software  
User-replaceable batteries  
Built-in USB communication port  
Compact design fits on/under your desk; can also be mounted to a wall  
Unit inspection  
Once you have received the Powerware 3105 UPS product, you should remove and  
inspect the product for shipping damage. If any damage is found, please notify the  
carrier and your dealer. Please keep the shipping carton and the packing foam in the  
event the product must be returned to the factory for service.  
Eaton Power Quality Pty Ltd  
10 Kent Road Mascot NSW 2020  
Phone: +61-2-9693 9366  
Fax: +61-2-8338 1159  
4
UserÊs Manual 350-700VA Rev B  
 
Safety Instructions  
ATTENTION  
!
Maintenance, other than battery replacement must be performed by a  
qualified technician. Failure to do so could result in an electrical shock.  
Although the unit may be unplugged from utility power, hazardous  
voltage still may be present through the battery.  
1.  
2.  
3.  
Place the Powerware 3105 UPS indoors in an area that has adequate airflow and  
is free of excessive dust. Do NOT allow the UPS to be exposed to moisture, rain,  
excessive heat, or direct sunlight.  
Use of the Powerware 3105 UPS product in life support applications, where failure  
of this equipment can reasonably be expected to cause failure of life support  
equipment or to significantly affect its safety or effectiveness is NOT recommended.  
Shut off the UPS and disconnect the input power cord from the wall outlet before  
replacing the battery.  
4.  
5.  
6.  
When replacing the battery, use the same number and type of battery  
Do NOT dispose of battery in a fire. The battery may explode.  
Do NOT open or mutilate the battery. They contain an electrolyte that is toxic and  
harmful to the skin and eyes.  
7.  
8.  
Proper disposal of the battery is required. Please refer to your local laws/regulations  
regarding battery disposal.  
Use tools with insulated handles to replace the battery to avoid personal injury. Due  
to energy hazard, please remove wristwatches and jewelry such as rings when  
replacing battery.  
5
UserÊs Manual 350-700VA Rev B  
 
Battery connection required before use!  
Connecting the Battery:  
Principle shown below. For detailed information how to connect, please refer to battery  
replacement section.  
Installation and Operation:  
The following steps explain how to connect and operate the Powerware 3105 UPS.  
1.  
Connect the UPS to a grounded power outlet.  
Note  
It is recommended that the battery should be charged for minimum 8 hours  
to ensure full charge before placing the UPS in service.  
2.  
Plug your computer, monitor or load to be protected into the „Battery Backup &  
Surge Protection‰ outlets. (These outlets will provide emergency battery backup  
power during power outages as well as protection from surges and spikes.)  
Do NOT plug LASER PRINTERS into the „Battery Backup‰ outlets.  
Do NOT plug ACCESSORY SURGE strips into the „Battery Backup‰ outlets.  
3.  
Plug your peripheral equipment or non-critical loads (printer, scanner, fax, speaker,  
etc.) into the „Surge Protection‰ outlets. (These outlets provide surge and spike  
protection only, they will NOT provide battery backup power during a utility power  
failure).  
4.  
5.  
6.  
7.  
Connect your computer to the UPS using USB cable provided.  
With your equipment turned off, switch on the UPS.  
When the „On/Off‰ LED light is illuminated, turn on the connected equipment.  
Install Power management software provided with the UPS  
6
UserÊs Manual 350-700VA Rev B  
 
Indicators  
5
1
2
4
3
1.  
On/Off Push Button/Test Switch  
One switch controls the power to your equipment. Upon power turn on, unit  
performs a self-test to detect overload or undercharged conditions.  
Turn on the UPS  
Press and hold the push button switch depressed for more than one second.  
Release the switch after the audible beep is sounded.  
Turn off the UPS  
Press and hold the push button switch for more than one second and release the  
switch after the audible beep is sounded. The UPS will shut down.  
Self-Test  
The UPS performs a self-test for about 3 seconds when the UPS is turned on.  
2.  
3.  
On/Off Battery LED  
Indicates the UPS is on and is powering your equipment.  
A constantly illuminated LED indicates normal utility power operation.  
A blinking LED indicates that the UPS is providing power from its battery.  
Fault/Warning LED  
Indicates a fault or warning condition is present.  
A constantly illuminated LED indicates a LOW battery condition.  
A blinking LED indicates the UPS is overloaded.  
4.  
5.  
Battery Backup & Surge Protection Outlets  
(3) Australian 10 Amp output receptacles that provide both battery backup and surge  
protection.  
Surge Protection Outlets  
3) Australian 10 Amp output receptacles that provide surge and spike protection.  
7
UserÊs Manual 350-700VA Rev B  
 
9
6
7
8
6.  
7.  
RJ11 Phone/Fax Protection Connectors  
USB Communication Port  
The provided LanSafe monitoring and shutdown software can be automatically  
configured to save your files and shut down your computer in the event of a  
prolonged power outage.  
Your personal computer can receive the status as utility power line, utility power  
failure, on battery and low battery by contact closure signals that are sent through  
the USB port.  
8.  
9.  
Circuit Breaker (resetable)  
The button protrudes out when an overload condition occurs. If the button protrudes  
out, then disconnect some non-essential equipment and reset the circuit breaker by  
pushing the button inward.  
Power connector  
10 Amp IEC to 10 Amp Australian input lead provided.  
Battery Replacement procedure:  
1.  
2.  
3.  
4.  
Batteries must be replaced with identical type.  
Disconnect UPS system from power source  
Open battery door.  
Disconnect used battery. Connect new battery. (It is important that connectors be  
firmly attached to new batteries.  
5.  
6.  
Close battery door.  
Properly recycle used battery.  
350VA and 500VA models (12V-4.5Ah,or 5Ah battery)  
8
UserÊs Manual 350-700VA Rev B  
 
700VA model (12V- 7Ah battery)  
Status Indicators  
The UPS provides both visual and audible status indicators. Visual indicators consist of  
three LEDs to represent the following conditions:  
On utility power operation  
On battery power operation  
UPS fault/alarm  
9
UserÊs Manual 350-700VA Rev B  
 
LED & Alarm Status Table  
UPS status  
Green LED  
Red LED  
Buzzer  
Self test  
Blink 1 (by turns)  
B1  
OFF  
OFF  
B5  
Charging  
ON  
ON  
OFF  
OFF  
Charge off  
Low battery  
Over load  
Normal  
AC (Utility mode  
ON  
Blink 2  
Blink 2  
OFF  
ON  
B4  
Blink 2  
Blink 2  
Blink 2  
OFF  
B1  
DC (Battery  
Mode)  
Over load  
Low battery  
OFF  
B1  
Blink 2  
ON  
B3  
Short/Fault/DC Over-Bat  
AC Over-Bat/Bat Fault  
ON  
B5  
OFF  
Blink 2  
Notes:  
Blink 1: ON 0.5 seconds / OFF 0.5 seconds  
Blink 2: ON 0.25 seconds / OFF 0.25 seconds  
B1: 1 beep / 5 seconds ON 0.25 seconds / OFF 4.75 seconds  
B3: 2 beeps / 5 seconds ON, 0.25 seconds / OFF 0.25 seconds 2 times 4 seconds OFF  
B4: ON 0.5 seconds / OFF 0.5 seconds  
B5: 3 beeps / 5 seconds ON 0.25 seconds / OFF 0.25 seconds 3 times 3.5 seconds OFF  
Specification*:  
Rating  
350VA  
500VA  
700VA  
Part Number  
Capacity  
31050350A  
350VA/210W  
180x280x115  
4.5  
31050500A  
500VA/300W  
180x280x115  
5
31050700A  
700VA/420W  
180x280x115  
6.5  
Dimensions (mm) HxWxD  
Unit Weight (kg)  
Input Connection  
1.8 metre line cord IEC to Australian 10Amp Plug  
Output Connection  
6 Australian 10Amp Outlets (3 Battery Backup & Surge Protection,  
3 Surge Protection only)  
Operation  
Input Voltage Range  
Output Voltage Range  
On Battery Output Voltage  
Frequency  
0-300 VAC  
Nominal -18% to +10%  
Nominal -12% to +10%  
50 Hz  
Lightning/Surge Protection  
Safety  
476 joules  
AS/NZS62040.1.1, AS/NZS60950, A-Tick  
AS/NZS62040.2, AS/NZSCISPR22, C-Tick  
2-6 msec. typical  
EMI  
Transfer Time to Battery/AC  
Battery Type  
Sealed, maintenance free lead-acid battery  
3 minutes at full rated load  
RJ11  
Typical Backup Time  
Internet/Phone/Fax Protection  
Short Circuit Protection  
Communication Port  
Environmental  
Circuit Breaker  
USB  
Operation Temperature  
Operation Relative Humidity  
Storage Temperature  
Software  
0oC - 40oC  
0 to 95% non condensing  
-15oC - 50oC  
Powerware LanSafe Software is included free of charge  
Optional Extended Warranty and On Site Changeover service plans available  
Service Plans  
*Due to continuing product improvement programs, specifications subject to change without notice  
10  
UserÊs Manual 350-700VA Rev B  
 
Troubleshooting  
Symptom  
Possible Cause  
Action to Take  
The battery is disconnected  
and utility power is not  
available at the wall outlet.  
Connect the battery (see Connect  
Battery) and ensure power is  
available at the wall outlet.  
UPS will not turn on  
Reduce the amount of equipment  
plugged into the outlets of the UPS.  
Next, reset the circuit breaker by  
pushing the plunger back in.  
Input Circuit Breaker has  
tripped.  
UPS is making a  
The „Battery Backup &  
Surge Protection‰ outlets are  
overloaded.  
Turn off the UPS and reduce the  
amount of equipment connected to  
these outlets.  
continuous sound  
and the „Overload‰  
indicator is lighted.  
Removed all connected equipment  
from the UPS and charge the  
battery at least 8 hours.  
During this charging period, turn  
off the UPS to prevent unnecessary  
discharging.  
The battery is not fully charged.  
UPS does not provide  
expected runtime.  
Call for service or you can replace  
the battery by ordering one from  
your dealer.  
Battery is getting older.  
The UPS is overloaded.  
Reduce the amount of equipment  
plugged into the outlets of the UPS.  
Try reducing the load by removing  
one piece of equipment at a time to  
determine if the problem continues.  
The UPS will turn off when the  
battery has been depleted during an  
extended power outage. Allow the  
UPS to re-charge the battery, before  
continuing on battery operation.  
The UPS has exhausted its  
available run time.  
Connected equipment  
loses power while  
connected to the UPS  
Ensure the equipment that is to be  
protected from a power outage is  
plugged into the „Battery Backup &  
Surge Protection‰ outlets.  
Equipment is connected to the  
„Surge Protection‰ outlets.  
Contact Powerware Technical  
Support  
The UPS may require service.  
Service and Support  
For questions and/or problems, please call your local distributor or the help desk and ask  
for a UPS technical representative.  
Powerware National Service Centre  
1300 303 059  
Please have the following information ready  
Model number and Serial number  
Symptoms of failure or problem  
Customer contact information  
11  
UserÊs Manual 350-700VA Rev B  
 
Head Office  
Eaton Power Quality Pty Ltd  
ABN 82 054 056 709  
10 Kent Road, Mascot NSW 2020  
Sales Offices  
Queensland  
Victoria  
Western Australia/NT  
South Australia  
Sales Phone:  
1300 UPS UPS  
Sales Email: [email protected]  
National Service Centre: 1300 303 059  
12  
UserÊs Manual 350-700VA Rev B  
 

Cooline Air Conditioner PT036 User Manual
Creda Cooktop S911E User Manual
Delta Electronics Power Supply SIC73 User Manual
Desa Oven SDVBND User Manual
Dynalink Network Router RTA770W User Manual
Escali Scale Plena User Manual
Frigidaire Cooktop FGGC3645K S W B User Manual
GE Monogram Ventilation Hood ZV30 ZV36 ZV48 User Manual
Global Machinery Company Drill BL1181 User Manual
Global Machinery Company Edger PEDG User Manual